Accuracy
- ± (0.10° C (0.18° F) + 0.10 % of Calibrated Span) with Two-Point Calibration
Electrical - Free Leads
- 22 AWG, 12” Long Extension Wire
Environmental Protection
- IP67 Hermetically Sealed
- NEMA 6P Hermetically Sealed
Input Impedance
- 1,000 ohms Min. (of Measuring Device, for Voltage Output)
Instrument Connection
- 1/2” NPS Male
- 1/2” NPT Male
Materials of Construction
- Armor & Overbraid: Stainless Steel
- Shrink for Teflon Cable: Polyolefin
NPT Connection
- 1” NPT Male
- 1/2” NPT Male
- 1/4” NPT Male
- 1/8” NPT Male
- 3/4” NPT Male
- 3/8” NPT Male
Operating Pressure
- Sensor psig: 500 (kPa: 3,447, bar: 34.47)
Operating Temperature
- -50° to 200° C (-58° to 392° F)
Output
- 0-10 Vdc Linear to Temperature
- 0-5 Vdc Linear to Temperature
- 1-5 Vdc Linear to Temperature
- 4-20 mA Loop Powered, Linear to Temperature
Power Supply
- 12-32 Vdc Polarity Protected
Process Connection Material
Sensor Circuit
- 2.5 mA Downscale for 4-20 mA Output
- 24 mA Upscale for 4-20 mA Output
Sensor, Probe Diameter
- 1/8 to 1/2” (3.17 to 12.7 mm)
Sensor, Probe Material
- 316 Stainless Steel
- 316L Stainless Steel
Stability
- Long Term Drift: ≤ 0.1 % of Full Scale Per Year
Storage Temperature
- -40° to 80° C (-40° to 176° F)
Temperature Range
- Sensor: -200° to 600° C (-328° to 1,112° F)
Wetted Materials
- 316 Stainless Steel, Dual Certified
- 316L Stainless Steel, Dual Certified