R25 Capsule RTD

Brand: Intempco Controls, Inc

Specifications
  • M12 connector ideal for quick disconnect applications and hermetically sealed
  • M12 extension cable available
  • Adjustable fittings available
  • Many fitting sizes and probe diameters available
  • RTD Pt100 ohm standard, others available
  • 2, 3 or 4-Wire circuit types
  • Isolation 1,000 Vdc
  • Factory calibration certificate optional

Specifications

Cable Length

  • Extension: 16.40 feet (5 metres)
  • Extension: 6.56 feet (2 metres)

Cable Material

  • Extension Cable Moulded PVC

Electrical Connectors

  • M12 Micro-Male Connector

Environmental Protection

  • IP67
  • IP68
  • NEMA 6P

Materials of Construction

  • Ferrule Material: Brass
  • Ferrule Material: Stainless Steel
  • Ferrule Material: Teflon

NPT Connection

  • 1” NPT Male
  • 1/2” NPT Male
  • 1/4” NPT Male
  • 1/8” NPT Male
  • 3/4” NPT Male
  • 3/8” NPT Male

Process Connection Material

  • Brass
  • Stainless Steel

RTD Type

  • Pt100 ohm at 0° C (32° F), α = 0.00385 DIN EN 60751
  • Pt1000 ohm at 0° C (32° F), α = 0.00385 DIN EN 60751

Sensor, Probe Connection

  • 2-Wire (Single/Dual)
  • 3-Wire (Single/Dual)
  • 4-Wire (Single/Dual)

Sensor, Probe Diameter

  • Probe: 1/8 to 3/8” (3.2 to 9.5 mm)

Sensor, Probe Material

  • Probe: 316 Stainless Steel

Temperature Range

  • -200° to 600° C (-328° to 1,112° F)

Tolerance

  • Element: ± 0.04 % (± 0.1° C) at 0° C (32° F), Class AA
  • Element: ± 0.06 % (± 0.15° C) at 0° C (32° F), Class A
  • Element: ± 0.12 % (± 0.3° C) at 0° C (32° F), Class B

Documentation

show more